1. INTRODUCTION
Input resistance
|
Current ≤ 150Ω Voltage ≥ 1MΩ Electric Couple ≥ 1MΩ
|
Input Maximum Current Maximum Limit
|
≤50mA
|
Resistance
|
Open circuit voltage is 2.5V Excitation current is 0.25mA
|
Output load capacity
|
Current ≤250Ω Voltage ≥250KΩ
|
Output Signal
|
AC220V/3A DC24V/3A
|
Measurement accuracy
|
0.5%FS ±1 byte
|
Setting method
|
Panel touch key digital setting; parameter setting value password lock setting value power off permanent storage
|
Display method
|
-1999~9999 measuring value display, LED working status display
|
Ambient temperature
|
0~50ºC
|
Relative humidity
|
≤85%RH
|
Operating power
|
Default AC220V(50-60HZ)
Customizable AC/DC 100-250V (switching power supply) DC24V |
Power consumption
|
≤5W
|
Structure
|
Standard snap-in type
|
Communication Protocol
|
Standard MODBUS communication protocol,
RS485 distance communication up to 1 km
RS232 communication distance up to 15 meters (when the instrument with communication, communication converter is best to use the active converter) |