Welcome to Jiangsu Aice Instrument Technology Co., Ltd.
Pseudolaric acid: Three-Phase AC Transmitter
Installation: Securely mounted using flat screw fixing.
Primary rated current: Options available are 1A, 5A, 10A, 20A, 50A, 80A, 100A, 150A, 200A, 300A, and 400A.
Primary edge measurement range: 2A to 450A.
Rated Auxiliary Output: Configurable to 1V, 10V, DC 0-20mA, DC 4-20mA, or as specified by the user.
Auxiliary power: Available in DC 12V or DC 24V.
Load capacity: Voltage output handles 5mA; Current output handles up to 6V. Accuracy is maintained at 0.5%.
Overload capacity: Can withstand up to 30 times the nominal input.
Isolated Withstand Voltage: Rated at 2.5kV/50Hz for 1 minute.
Lossy voltage: <10mV
Temperature drift: <500PPMC
Linearity: Ensured at 0.1%.
Bandwidth: Ranges from 20Hz to 5KHz.
Overload capacity: <15mA + output current
Response time: <200mS
Operating temperature: Functional within a range of -10°C to 70°C.
Storage temperature: Safely stored between -25°C and 85°C.
1. Q: Can I buy any of your product accessories?
A: Yes, you can. Most accessories are available for purchase. However, some items with patented designs or intellectual property restrictions may not be available.
For more details, please reach out to our sales team.
2. Q: Can I be your exclusive distributor?
A: Yes. However, this depends on your annual purchase volume and our mutual long-term relationship. We seek business partners who can establish and maintain a long-term, trust-based relationship.